Genie systems flexible drop enhances work efficiency by 70-80% compared to conventional piping. We designed anchoring parts specially to allow for an easy and problem free installation even when the task is performed by an unskilled installer in a very restricted space.

Free of problem : Genie systems flexible drop will give answers to the various problems arise from installing flexible drop in the suspended ceiling.

Satety : One of the crucial factor in of Flexible drop’s performance is the shape of Gasket which has very important role in connecting the Flexible drop to its inlet and outlet reducer.

Ring type gasket can be damaged while connecting the inlet or outlet reducer to the flexible hose. It can be twisted and the twisted Ring type gasket will make uneven contact to the hose and inlet, outlet reducer and become the cause of leakage in the long term. Genie systems designed the Flexible drop safe in any circumstances.

Genie systems flexible drop hasn’t just passed UL, LPCB and FM test. Genie systems test it’s products everyday by the standard of UL and FM in the Lab

SPECIFICATIONS:

Lengths Available 700mm,1000mm,1200mm, 1500mm, 1800mm   Hose Stainless Steel 304  
Outlet 1/2” or 3/4”   Nut & Nipple Zinc-Plated Steel  
Hose Type Unbraided   Sealing Gasket / Isolation Ring EPDM / NYLON  
           
Max. Ambient Temperature Rating 225F   Minimum Bend Raius 100mm(UL/ULC) From connection nuts
Max. Working Pressure Rating 175 psig (UL/ULC)   Connection Inlet 1”NPT or BSP
* Required torque to assemble reducer and nipple with the flexible hose : 300 kgf.cm   Outlet

1/2” or 3/4”NPT or BSP




FRICTION LOSS DATA :

Model Rated Pressure
psig
Max. Ambient
Temp
°F
Nom. Inlet by Outlet Size
in.
Assembly Length
ft (mm)
Max No. of 
90° Bends
Min Bend Radius,
mm.
Equivalent Length of 1 in. Schedule 40 Steel Pipe (C = 120), 
ft
Flexibility Type
DJ25UB-700 175 225 1x1/2 700 1 100 24 Limited
DJ25UB-1000 175 225 1x1/2 1000 2 100 44 Limited
DJ25UB-1200 175 225 1x1/2 1200 2 100 49 Limited
DJ25UB-1500 175 225 1x1/2 1500 2 100 59 Limited
DJ25UB-1800 175 225 1x1/2 1800 3 100 84 Limited
DJ25UB-700 175 225 1x3/4 700 1 100 30 Limited
DJ25UB-1000 175 225 1x3/4 1000 2 100 48 Limited
DJ25UB-1200 175 225 1x3/4 1200 2 100 55 Limited
DJ25UB-1500 175 225 1x3/4 1500 2 100 64 Limited
DJ25UB-1800 175 225 1x3/4 1800 3 100 86 Limited
  • UL : 100mm minimum bend radius, where C=120

SPECIFICATIONS:

Lengths Available

700mm, 1000mm,1200mm, 1500mm, 1800mm

 

Hose

Stainless Steel 304

 

Outlet

1/2” or 3/4”

 

Nut & Nipple

Zinc-Plated Steel

 

Hose Type

Unbraided

 

Sealing Gasket / Isolation Ring

EPDM / NYLON

 
           

Max. Ambient Temperature Rating

225F

 

Minimum Bend Raius

 

Max. Working Pressure Rating

16 BAR( LPCB )

 

Connection

Inlet

1”NPT or BSP

* Required torque to assemble reducer and nipple with the flexible hose : 300 kgf.cm

 

Outlet

1/2” or 3/4”NPT or BSP


FRICTION LOSS DATA

Table 1

       

Summary of pressure loss & equivalent length for 700 mm flexible hose with one 90° bend and terminated in a Y” outlet reducer

Flow rate (l/min)

Pressure

upstream(bar)

Pressure

downstream(bar)

Corrected pressure loss (bar)

Eqivalent Length

40

0.31

0.2

0.005

0.4

60

0.75

0.49

0.077

3

80

1.43

0.93

0.199

4.56

100

2.22

1.44

0.321

4.89

120

3.22

2.08

0.483

5.23

150

5.01

3.23

0.751

5.38

Average equivalent length - 3.90

   
         

Table 2

       

Summary of pressure loss & equivalent length for 1000 mm flexible hose with two 90° bends and terminated in a straight V” outlet reducer

Flow rate (l/min)

Pressure

upstream(bar)

Pressure

downstream(bar)

Corrected pressure loss (bar)

Eqivalent Length

40

0.34

0.2

0.035

2.88

60

0.93

0.52

0.227

8.86

80

1.66

0.92

0.439

10.06

100

2.62

1.43

0.731

11.09

120

3.79

2.05

1.083

11.73

150

6.05

3.24

1.781

12.76

Average equivalent length - 9.56

   
         

Table 3

       

Summary of pressure loss & equivalent length for 1200 mm flexible hose with two 90° bends and terminated in a straight V` outlet reducer

Flow rate (l/min)

Pressure

upstream(bar)

Pressure

downstream(bar)

Corrected pressure loss (bar)

Eqivalent Length

40

0.36

0.2

0.055

4.53

60

0.97

0.52

0.267

10.42

80

1.73

0.92

0.509

11.67

100

2.75

1.43

0.861

13.06

120

4.02

2.07

1.293

14

150

6.32

3.21

2.081

14.91

Average equivalent length - 11.43

   
         

Table 4

       

Summary of pressure loss & equivalent length for 1500 mm flexible hose with two 90° bends and terminated in a straight V` outlet reducer

Flow rate (l/min)

Pressure

upstream(bar)

Pressure

downstream(bar)

Corrected pressure loss (bar)

Eqivalent Length

40

0.37

0.2

0.065

5.36

60

0.98

0.52

0.277

10.81

80

1.76

0.93

0.529

12.13

100

2.77

1.43

0.881

13.37

120

4.03

2.08

1.313

14.22

150

6.35

3.22

2.101

15.06

Average equivalent length - 11.82

   
         

Table 5

       

Summary of pressure loss & equivalent length for 1800 mm flexible hose with three 90° bends and terminated in a straight V` outlet reducer

Flow rate (l/min)

Pressure

upstream(bar)

Pressure

downstream(bar)

Corrected pressure loss (bar)

Eqivalent Length

40

0.4

0.19

0.105

8.66

60

1.05

0.51

0.357

13.93

80

1.93

0.92

0.709

16.25

100

3.05

1.44

1.151

17.46

120

4.38

2.05

1.673

18.12

150

7.04

3.25

2.761

19.79

Average equivalent length - 15.70

   

LUAN DUNG.,JSC

To use the word "Dung" (Impartiality) to raise the Name is to shine the light on truth, to use the word "Luan" (Interpretation) to call the Name, is to understand the words. If the truth is not Named, it cannot enlighten, and so it is bound to "Dung" in order to be portrayed. Words, when unexplained, cannot be understood, so we must utilize "Luan" in order to to illustrate. When the truth has been portrayed, the words has been illustrated, then the practice and introspection can be left hanging. That is clear.