Flexible Sprinkler Drops

GENIE SYSTEMS Flexible Sprinkler Joint are designed to significantly reduce labor and installation costs. By eliminating the need for pipe cutting and midline connections, you save valuable time and money.

Genie Systems flexible sprinkler connections offer braided and unbraided flexible hoses in 700mm,1000mm,1200mm and 1800mm with top loading or front loading

brackets for variety of ceiling and wall applications:T-Bars, metal studs, hat channels, wood beams, concrete sidewalls, and more. The system is qualified to be

installed at commercial, hotel, retail, restaurants, cultural, entertainment, educational, government, healthcare, and religious buildings.

GENIE SYSTEMS Flexible Sprinkler Drops Appliance Standards

1. Underwriter’s Laboratories, Inc. (UL/ULC), cUL us 2443:

·         Standard for flexible sprinkler hose with fittings for fire protection service

2. Loss Prevention Certification Board (LPCB):

·         LPS 1262 : Standard for TESTING FLEXIBLE HOSES FOR SPRINKLER SYSTEMS

3. National Fire Protection Association (NFPA):
  • NFPA 13 : Standard for the Installation of Sprinkler Systems
  • NFPA 13D : Standard for the Installation of Sprinkler Systems in One and Two-Family Dwellings and Manufactured Homes
  • NFPA 13R : Standard for Installation of Sprinkler Systems in residential Occupancies up to and including four stories in height
  • NFPA 13 Section 9.2.1.3.3.3 : No hangers are require long as the length does not exceed 6ft.
4. American Society for Testing and Methods (ASTM):
  • ASTM C635 : Standard specifications for the manufacture, performance, and testing of metal suspension systems for acoustical tile and lay-in panel ceilings
  • ASTM C636 : Standard practice for installation of metal ceiling suspension systems for acoustical tile and lay-in panels
5. International Building Code (IBC) Section 1621 / American Society of Civil Engineers (ASCE) 7.9.6.2.6.2 & 9.6.2.6.2.2:
  • Flexible Sprinkler Connections are an alternative solution to install without seismic escutcheons
 

Temperature

225 oF

 

Working pressure

175 psi

 

Maximum Bend Radius

4”(UL type), 8”(FM type)

 

K-Factor

1/2” Outlet

5.6 gpm (UL, FM model)

3/4” Outlet

11.2 gpm(UL), 8.0gmp(FM)

Diameter of hose

UL listed unbraided hose

25.0 mm

UL listed braided hose

26.8 mm

FM listed braided hose

26.8 mm

FM listed braided hose

28.0 mm

 

Length

Nominal Inlet by Outlet Size,in.

Assembly
Length, (units)

Max No. of
90° Bends

Min Bend
Radius (units)

Equivalent Length of 1 in. Schedule 40 Steel Pipe (C = 120), ft

700

1/2”, 3/4”

700

UL (1) FM (1)

100

UL Type (24, 30)  FM Type (17.9, 14.4)

1000

1/2, 3/4”

1000

UL (2) FM(1)

100

UL Type (44, 48)  FM Type (22.2, 18.3)

1200

1/2, 3/4”

1200

UL (2) FM(4)

100

UL Type (49, 55)  FM Type (37.0, 32.8)

1500

1/2, 3/4”

1500

UL: (2) FM(4)

100

UL Type (59, 64)  FM Type (45.5,43.2)

1800

1/2, 3/4”

1800

UL (3) FM(5)

100

UL Type (84, 86)  FM Type (63.0,58.7)

 

 

Length

700,1000,1200,1500,1800mm

Reducing nipple Dia

1/2”, 3/4” NPT or BSPT (Straight or 90 degree elbow)

Type

Unbraided

UL certificate

Braided (ø 26.8)

UL and FM approval

Braided (ø 28.0)

FM approved

 

LUAN DUNG.,JSC

To use the word "Dung" (Impartiality) to raise the Name is to shine the light on truth, to use the word "Luan" (Interpretation) to call the Name, is to understand the words. If the truth is not Named, it cannot enlighten, and so it is bound to "Dung" in order to be portrayed. Words, when unexplained, cannot be understood, so we must utilize "Luan" in order to to illustrate. When the truth has been portrayed, the words has been illustrated, then the practice and introspection can be left hanging. That is clear.